Certification for numerous designs has been attained by P.M. switchboards in its pursuit of technical excellence. The company has been undertaking tests at Testing & Certification Australia (formally known as the Sydney County Council) since 1973. Our certification includes for the following:
In January 2009, we successfully completed a full range of Type Tests on Prototype Switchboards to AS/NZS 3439.1:2002 as follows:
Clause 8.2.1 Temperature Rise Limits
Clause 8.2.2 Dielectric Properties
Clause 8.2.3.2.3 a & b Rated Conditional Short Circuit Currents at 50KA
& 80KA
Clause 8.2.3.2.3 b Rated Peak and Short Time withstand currents at
65KA rms for 1 sec, 143KA peak
80KA rms for 1 sec, 176KA peak
100KA rms for 1 sec, 220KA peak
Clause 8.2.3.2.3 d Rated Peak and Short Time withstand currents at
60KA rms for 1 sec, 132 KA peak
Clause 8.2.4 Effectiveness of Protective Circuit
Clause 8.2.5 Clearance and Creepage Distances
Annex ZD Standard & Special Internal Arcing Fault Tests
Our certification for full type test certification includes the following: -
Short Circuit Tests 25Ka through to 80Ka for 1 to 3 seconds
Through Fault Tests to 80Ka
Arc Fault Containment
Temperature Rise Tests
IP Rating Test.
Protective Circuit Tests
Mechanical Operations
High Voltage Tests